Cape Care for Women: St. Francis Medical Campus

Water was coming through the north elevation at the Cape Care for Women building on the St. Francis Medical Campus, and the contractor needed to know whether the windows, the wall behind them, or the transition at the lower entrance roof was the source. A unit had already been pulled to expose as-built conditions.

G&W spent two consecutive days on site with a two-person team, testing windows to AAMA 501.2 where access allowed and running fifteen-minute water cascades at upper areas of concern along with sill dam testing. Removal of additional units was observed directly. Upper elevations out of reach were surveyed by UAV under an FAA Part 107 pilot, working within airspace limits near an active medivac facility. Findings, probable causes, and remediation options were delivered in a written report.

Location:
Cape Girardeau, MO

Client Type:
General Contractor

Testing Scope:
North elevation windows, lower roof, UAV survey above

Market:
Healthcare

METHODS & STANDARDS

AAMA 501.2

Water infiltration at fixed glazing

Water Cascade Testing

Fifteen-minute application at upper areas

Sill Dam Testing

Drainage path at window sill verified

Infrared and Moisture Survey

Concealed wetting located behind assemblies

OUR APPROACH

Pre-Mobilization Review

Client photos, north elevation conditions

AAMA 501.2 Window Testing

Accessible units, 15-minute water cascade

Sill Dam and Removal Observation

Units pulled, as-built conditions exposed

UAV Elevation Survey

Part 107 pilot, upper north elevation

Reporting

Causes, remediation options, written findings